Parameters
vacon • 86
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.8
Group 3.7: Prohibit Freq
In some systems it may be necessary to avoid certain frequencies due to mechanical reso-
nance problems. By setting up prohibit frequencies it is possible to skip these ranges. When
the (input) frequency reference is increased, the internal frequency reference is kept at the low
limit until the (input) reference is above the high limit.
6.1.9
Group 3.8: Supervisions
Choose here:
1.
one or two (P3.8.1/P3.8.5) signal values for supervision.
2.
whether the low or high limits are supervised (P3.8.2/P3.8.6)
3.
the actual limit values (P3.8.3/P3.8.7).
4.
the hystereses for the set limit values (P3.8.4/P3.8.8).
Table 70. Prohibit frequencies
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.7.1
Range 1 Low Lim
-1,00
320,00
Hz
0,00
509
0 = Not used
P3.7.2
Range 1 High Lim
0,00
320,00
Hz
0,00
510
0 = Not used
P3.7.3
Range 2 Low Lim
0,00
320,00
Hz
0,00
511
0 = Not used
P3.7.4
Range 2 High Lim
0,00
320,00
Hz
0,00
512
0 = Not used
P3.7.5
Range 3 Low Lim
0,00
320,00
Hz
0,00
513
0 = Not used
P3.7.6
Range 3 High Lim
0,00
320,00
Hz
0,00
514
0 = Not used
P3.7.7
0,1
10,0
Times
1,0
518
Multiplier of the currently
selected ramp time between
prohibit frequency limits.
Table 71. Supervision settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.8.1
Superv1 Item
0
11
0
1431
0 = Output frequency
1 = Frequency reference
2 = Motor current
3 = Motor torque
4 = Motor power
5 = DC-link voltage
6 = Analogue input 1
7 = Analogue input 2
8 = Analogue input 3
9 = Analogue input 4
10 = Analogue input 5
11 = Analogue input 6
P3.8.2
Superv1 Mode
0
2
0
1432
0 = Not used
1 = Low limit supervision
(output active under limit)
2 = High limit supervision
(output active over limit)
P3.8.3
Superv1 Limit
-50.00
50.00
Varies
25.00
1433
Supervision limit for selected
item. Unit appears automati-
cally.
P3.8.4
Superv1 Hyst
0.00
50.00
Varies
5.00
1434
Supervision limit hysteresis
for selected item. Unit is set
automatically.
P3.8.5
Superv2 Item
0
11
1
1435 See P3.8.1
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......