7
vacon • 165
Fault
101
1101
Process supervi-
sion fault (PID1)
PID controller: Feedback value outside
of supervision limits (and the delay if
set).
Check settings.
105
1105
Process supervi-
sion fault (PID2)
PID controller: Feedback value outside
of supervision limits (and the delay if
set).
Check settings.
109
1109
Input pressure
supervision
Input pressure supervision signal has
gone below the alarm limit.
Check the process.
Check the parameters
Check the input pressure sen-
sor and connections.
1409
Input pressure supervision signal has
gone below the fault limit.
111
1315
Temperature
fault 1
At least one of the selected tempera-
ture input signals has reached the
alarm limit.
Find the cause of temperature
raise.
Check the temperature sensor
and connections.
Check that the temperature
input is hardwired if no sensor
is connected.
See option board manual for
further information.
1316
At least one of the selected tempera-
ture input signals has reached the fault
limit.
112
1317
Temperature
fault 2
At least one of the selected tempera-
ture input signals has reached the fault
limit.
1318
At least one of the selected tempera-
ture input signals has reached the fault
limit.
Fault
code
Fault
ID
Fault name
Possible cause
Remedy
Table 125. Fault codes and descriptions.
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......