vacon • 93
Parameters
6
6.1.10.7
Group 3.9.8: AI Low Protection
6.1.10.8
Group 3.9.9: User Defined Fault 1
6.1.10.9
Group 3.9.10: User Defined Fault 2
Table 78. AI Low Protection settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.8.1
AI Low Protection
0
2
2
767
This parameter defines if the
AI Low protection is enabled
or disabled.
0 = Disabled
1 = Enabled in Run State
2 = Enabled in Run&Stop
States
P3.9.8.2
AI Low Fault
0
5
0
700
Response when an analogue
signal in use goes below 50%
of the minimum signal range.
0 = No action
1 = Alarm
2 = Alarm, Preset Freq
3 = Alarm, Previous Freq
4= Fault (Stop according to
stop mode)
5 = Fault (Stop by coasting)
Table 79. User Defined Fault 1 settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.9.1
User Defined Fault 1
DigIN
Slot0.1
1552
3
Digital input selection for
activating User Defined Fault
(1 or 2)
P3.9.9.2
UserDef. Fault1 Resp.
0
3
3
1552
5
0 = No action
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
Table 80. User Defined Fault 2 settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.10.1
User Defined Fault 2
DigIN
Slot0.1
1552
4
Digital input selection for
activating User Defined Fault
(1 or 2)
P3.9.10.2
UserDef. Fault2 Resp.
0
3
3
1552
6
0 = No action
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......