Parameters
vacon • 100
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.14
Group 3.13: PID Controller
6.1.14.1
Group 3.13.1: Basic Settings
Table 91. PID controller 1 basic settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.1.1
Gain
0.00
1000.00
%
100.00
118
If the value of the parameter
is set to 100% a change of
10% in the error value causes
the controller output to
change by 10%.
P3.13.1.2
Integration Time
0.00
600.00
s
1.00
119
If this parameter is set to
1,00s a change of 10% in the
error value causes the con-
troller output to change by
10.00%/s.
P3.13.1.3
Derivation Time
0.00
100.00
s
0.00
132
If this parameter is set to
1,00s a change of 10% in the
error value during 1.00 s
causes the controller output
to change by 10.00%.
P3.13.1.4
ProcessUnitSel.
1
38
1
1036 Select unit for actual value.
P3.13.1.5
ProcessUnitMin
Varies
Varies
Varies
0
1033
Value in Process units at 0%
feedback or setpoint.
This scaling is done for moni-
toring purpose only. The PID
controller still uses the per-
centage internally for feed-
backs and setpoints.
P3.13.1.6
ProcessUnitMax
Varies
Varies
Varies
100
1034 See above.
P3.13.1.7
ProcessUnitDeci
0
4
2
1035
Number of decimals for pro-
cess unit value
P3.13.1.8
Error inversion
0
1
0
340
0 = Normal (Feedback < Set-
point -> Increase PID output)
1 = Inverted (Feedback < Set-
point -> Decrease PID output)
P3.13.1.9
Varies
Varies
Varies
0
1056
Dead band area around the
setpoint in process units.The
PID output is locked if the
feedback stays within the
deadband area for a pre-
defined time.
P3.13.1.10
0.00
320.00
s
0.00
1057
If the feedback stays within
the dead band area for a pre-
defined time, the output is
locked.
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......