vacon • 89
Parameters
6
6.1.10.3
Group 3.9.3: Motor Stall
The motor stall protection protects the motor from short time overload situations such as one
caused by a stalled shaft. The reaction time of the stall protection can be set shorter than that
of motor thermal protection. The stall state is defined with two parameters, P3.9.3.2 (
). If the current is higher than the set limit and the output
frequency is lower than the set limit the stall state is true. There is actually no real indication
of the shaft rotation. Stall protection is a type of overcurrent protection.
NOTE!
If you use long motor cables (max. 100m) together with small drives (
≤
1.5
kW) the motor current measured by the drive can be much higher than the actual
motor current due to capacitive currents in the motor cable. Consider this when
setting up the stall protection functions.
Table 74. Motor stall protection settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.3.1
MotorStall Flt
0
3
0
709
0 = No action
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
P3.9.3.2
0.00
5.2
A
3.7
710
For a stall stage to occur, the
current must have exceeded
this limit.
P3.9.3.3
1.00
120.00
s
15.00
711
This is the maximum time
allowed for a stall stage.
P3.9.3.4
Stall Freq. Limit
1.00
Hz
25.00
712
For a stall state to occur, the
output frequency must have
remained below this limit for
a certain time.
13006.emf
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......