Startup
P1.22
I/O A Ref sel
1
9
5
117
Selection of ref source when
control place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P1.23
Keypad Ref sel
1
9
2
121
Selection of ref source when
control place is keypad:
See P1.22
P1.24
Fieldbus Ref sel
1
9
3
122
Selection of ref source when
control place is Fieldbus:
See P1.22
P1.25
AI1 signal range
0
1
0
379
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
P1.26
AI2 signal range
0
1
1
390
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
Table 1. Quick setup parameter group