vacon • 113
Parameters
6
6.1.18
Group 3.22: Solar
6.1.18.1
Group 3.22.1: Start Settings
6.1.18.2
Group 3.22.2: MPPT
Table 106. Start Settings parameters
Code
Parameter
Min
Max
Unit
Defau
lt
ID
Description
P3.22.1.1
Start DC Voltage
400
800
V
650
1916
DV voltage threshold level to
activate Run enable
P3.22.1.2
Short restart delay
0.1
5.0
m
1.0
1917
Delay time to restart
P3.22.1.3
Short restart delay tries
1
10
5
1918
Number of restart tries
P3.22.1.4
Long restart delay
6.0
30.0
m
10.0
1919
Long delay time to restart
Table 107. MPPT parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.22.2.1
Vmp at 100% power
400
800
V
600
1920
P3.22.2.2
Vmp at 10% power
400
700
V
540
1921
P3.22.2.3
Panel/Motor power
ratio
50.00
100.00
%
100.00
1922
P3.22.2.4
P gain
0.000
1.000
0.050
1923
Gain for internal PI regula-
tor. The internal frequency
reference keeps the panels
working on MPP.
P3.22.2.5
I gain
0.000
1.000
0.050
1924 Integration time.
P3.22.2.6
Acceleration time
0.1
60.0
s
1.0
1925
Time from minimum to
maximum frequency
P3.22.2.7
Deceleration time
0.1
60.0
s
1.0
1926
Time from maximum to
minimum frequency
P3.22.2.8
P&O update time
2
6
s
3
1939
P3.22.2.9
P&O voltage step
3
10
V
5
1940
P3.22.2.1
0
P&O power variation
0.2
5.0
%
1.0
1941
P3.22.2.1
1
P&O local max volt
step
20
60
V
30
1945
P3.22.2.1
2
P&O local max time
1
60
m
10
1946
P3.22.2.1
3
P&O local max freq
0.00
20.00
Hz
10.00
1947
P3.22.2.1
4
Damping sensitivity
5
50
V
10
1943
Amplitude of oscillation to
be recognized
P3.22.2.1
5
Damping time
3
10
s
4
1944
Time for the oscillations on
DC voltage
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......