Parameters
vacon • 150
Service support: find your nearest Vacon service center at www.vacon.com
6
6.2.22
Auto-Cleaning
P3.21.1.1
C
LEANING
FUNCTION
If Auto-cleaning function is enabled by parameter P3.21.1.1 the Auto-cleaning sequence will
start by activating the digital input signal selected by parameter P3.21.1.2.
P3.21.1.2
C
LEANING
ACTIVATION
See above.
P3.21.1.3
C
LEANING
CYCLES
The Forward/reverse cycle will be repeated for the amount of times defined by this parameter.
Auto-cleaning function is based on rapidly accelerating and decelerating the pump. The user
can define a forward/reverse cycle by setting parameters P3.21.1.4, P3.21.1.5, P3.21.1.6 and
P3.21.1.7.
See parameter P3.21.1.4 Clean Forward Freq. above.
See parameter P3.21.1.4 Clean Forward Freq. above.
See parameter P3.21.1.4 Clean Forward Freq. above.
C
LEANING
ACCELERATION
TIME
The user can also define separated acceleration and deceleration ramps for the Auto-cleaning
function with parameters P3.21.1.8 and P3.21.1.9.
C
LEANING
DECELERATION
TIME
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......