Parameters
vacon • 112
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.17
Group 3.21: Pump Control
6.1.17.1
Group 3.21.1: Auto-Cleaning
The Auto-cleaning function is used to remove any dirt or other material that may have attached
to the pump impeller. Auto-cleaning is used e.g. in wastewater systems to keep up the perfor-
mance of the pump. Auto Cleaning function can also be used to clear the blocked pipe or valve.
Table 105. Auto-cleaning parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.21.1.1
0
1
0
1714
0=Disabled
1=Enabled
P3.21.1.2
DigIN
Slot0.1
1715
Digital input signal used to
start the Auto Cleaning
sequence.
Auto-cleaning sequence will
be aborted if activation sig-
nal is removed before the
sequence has been com-
pleted.
NOTE:
The drive will start
if the input is activated!
P3.21.1.3
1
100
5
1716
Number of forward/reverse
cleaning cycles.
P3.21.1.4
Clean Forward Freq.
0.00
50.00
Hz
45.00
1717
Forward direction frequency
in Auto-cleaning cycle.
P3.21.1.5
0.00
320.00
s
2.00
1718
Running time for forward
direction frequency in Auto-
cleaning cycle.
P3.21.1.6
Clean Reverse Freq.
0.00
50.00
Hz
45.00
1719
Reverse direction frequency
in Auto-cleaning cycle.
P3.21.1.7
0.00
320.00
s
0.00
1720
Running time for reverse
direction frequency in Auto-
cleaning cycle
P3.21.1.8
0.1
300.0
s
0.1
1721
Motor acceleration time
when Auto-cleaning is active
P3.21.1.9
0.1
300.0
s
0.1
1722
Motor deceleration time
when Auto-cleaning is active
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......