vacon • 155
Parameters
6
P&O in local max points
A panel with partial irradiation, or somehow defective, could cause a discontinuity on the pow-
er/voltage curve of the array. In this situation the basic P&O logic (perturb and observe) could
lead to a local maximum point, that is not corresponding to maximum available power.
Figure 58.
P3.22.2.11 P&O
LOCAL
MAX
VOLT
STEP
To bypass discontinuity on power/voltage curve of array, after having reached a stable point,
the P&O takes a bigger downward step (P3.22.2.11) in voltage. This step allows to overcome
the local maximum and continue to search for the actual MPP.
If the point is the real MPP, the lower voltage reference will cause a drop in DC voltage and
some oscillations, that are recognized and automatically damped by increasing the DC voltage
reference.
The function can be disabled by programming P3.22.2.11= 0V.
P3.22.2.12 P&O
LOCAL
MAX
TIME
Further attempts to reach a higher MPP after an unsuccessful attempt will follow only after
the programmable masking time (P3.22.2.12).
P3.22.2.13 P&O
LOCAL
MAX
FREQ
The downward step is done only when output frequency is above minimum fre
P3.22.2.13.
Voltage across PV array (V)
P
o
w
e
r f
rom PV ar
ray (W
)
50
100
150
200
2
1.5
1
0.5
0
2.5
250
3
0
x10
4
P
MAX1
P
MAX2
P
MAX3
Local maximum points
Global maximum point
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......