8.2
VACON
®
100 - TECHNICAL DATA
Table 44: The technical data of the Vacon
®
100 AC drive
Technical item or function
Technical data
Mains connection
Input voltage U
in
208-240 V, 380-500 V, 525-600 V, 525-690 V, -10%…
+10%
Input frequency
50-60 Hz, -5...+10%
Connection to mains
Once per minute or less
Starting delay
6 s (MR4 to MR6), 8 s (MR7 to MR9)
Mains
•
Mains types: TN, TT, and IT
•
Short circuit current: the maximum short circuit
current must be < 100 kA.
Motor connection
Output voltage
0-U
in
Continuous output current
I
L
: Ambient temperature max. +40 °C overload 1.1 x I
L
(1 min/10 min)
I
H
: Ambient temperature max. +50 °C overload 1.5 x I
H
(1 min/10 min)
I
H
in 600/690 V drives: Ambient temperature max. +40
°C overload 1.5 x I
H
(1 min/10 min)
Output frequency
0-320 Hz (standard)
Frequency resolution
0.01 Hz
VACON · 128
TECHNICAL DATA, VACON® 100
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205