6
Put the cover of the drive back. Pull the RS485
cables to the side.
a
)
Keep the distance of the Ethernet, I/O and
Fieldbus cables from the motor cable at a
minimum of 30 cm (11.81 in).
b
)
Move the fieldbus cables away from the motor
cable.
A
A. The fieldbus cables
7
Set the bus termination for the first and the last
device of the fieldbus line. We recommend that the
first device on the fieldbus is the master device.
D
D
E
A
C
B
A. The termination is activated
B. The termination is deactivated
C. The termination is activated with a DIP
switch
D. The bus termination. The resistance is
220 Ω.
E. The fieldbus
VACON · 102