7
Put the cable entry plate with the cables into the
groove on the frame of the drive.
8
Connect the stripped cables.
a
)
Expose the shield of all the 3 cables to make a
360-degree connection with the grounding
clamps for cable shield.
b
)
Connect the phase conductors of the mains
cable and of the motor cable, and the
conductors of the the brake resistor cable into
the correct terminals.
c
)
Attach the grounding conductor of each cable
to a grounding terminal with a grounding
clamp for grounding conductor.
d
)
Make sure that the external grounding
conductor is connected to the grounding bar.
See chapter 2.4 Grounding and earth fault
protection.
e
)
See the correct tightening torques in Table 23.
Br
ak
e
cab
le
C
D
E
F
C
B
A
A. The grounding clamp for cable
shield
B. The terminals
C. The grounding terminal
D. The mains cable
E. The brake resistor cable
F. The motor cable
POWER CABLING
VACON · 73
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
5