5
Put the cables - the mains cable, the motor cable
and the optional brake cable - in the openings of
the cable entry plate.
a
)
Cut the grommets open to move the cables
through them. If the grommets fold in when
you put the cable, pull the cable back to make
the grommets straight.
b
)
Do not cut the grommet openings wider than
what is necessary for the cables that you use.
c
)
With the enclosure class IP54, the connection
between the grommet and the cable must be
tight. Pull the first bit of the cable out of the
grommet so that is stays straight. If this is not
possible, make the connection tight with some
insulation tape or a cable tie.
A
B
C
A. The mains cable
B. The brake cable
C. The motor cable
6
Remove the grounding clamps for cable shield and
the grounding clamps for grounding conductor. The
tightening torque is 2.2 Nm or 19.5 lb-in.
M4x16
(2.2 Nm)
VACON · 72
POWER CABLING
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205