Table 52: The technical data of the Vacon
®
100 HVAC AC drive
Technical item or function
Technical data
EMC (at default settings)
Immunity
Fulfils EN 61800-3 (2004), 1
st
and 2
nd
environment
Emissions
•
200-500 V: EN 61800-3 (2004), category C2.
•
600 V: EN 61800-3 (2004), category C3.
•
All: The product is configurable to category C4 for
installation on IT networks. The drive can be
modified for IT type mains. See chapter 7.6 Instal-
lation in an IT system. The IP00 / UL Open Type
drive has by default category C4.
Noise level
Average noise level (min-
max) sound pressure
level in dB(A)
The sound pressure depends on the cooling fan speed,
which is controlled in accordance with the drive tem-
perature.
MR4: 45-56
MR5: 53-65
MR6: 62-72
MR7: 43-73
MR8: 58-73
MR9: 54-75
Safety standards and cer-
tifications
EN 61800-5-1 (2007), CE, cUL (See the nameplate of
the drive for more approvals.)
VACON · 150
TECHNICAL DATA, VACON® 100 HVAC
10
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205