NOTE!
The frames MR7, MR8, and MR9 have the brake chopper, only if their type
designation code has the code +DBIN. The frames MR4, MR5, and MR6 have the
brake chopper as standard.
NOTE!
The Vacon
®
100 FLOW and HVAC software do not have the dynamic braking or the
brake resistor functions.
5.5
PREPARING FOR THE CABLE INSTALLATION
•
Before you start, make sure that none of the components of the AC drive is live. Read
carefully the warnings in chapter 2 Safety.
•
Make sure that the motor cables are sufficiently far from other cables.
•
The motor cables must cross other cables at an angle of 90°.
•
If it is possible, do not put the motor cables in long parallel lines with other cables.
•
If the motor cables are in parallel with other cables, obey the minimum distances (see
Table 20 The minimum distances between cables).
•
The distances are also valid between the motor cables and the signal cables of other
systems.
•
The maximum lengths of shielded motor cables are 100 m / 328 ft (for MR4), 150 m / 492
ft (for MR5 and MR6), and 200 m / 656 ft (for MR7, MR8, and MR9).
•
If the cable insulation checks are necessary, see chapter 7.4 Measuring the cable and
motor insulation for instructions.
Table 20: The minimum distances between cables
The distance between
cables [m]
The length of the
shielded cable [m]
The distance between
cables [ft]
The length of the
shielded cable [ft]
0.3
≤ 50
1.0
≤ 164.0
1.0
≤ 200
3.3
≤ 656.1
5.6
CABLE INSTALLATION
5.6.1
FRAMES MR4 TO MR7
Table 21: The cable stripping lengths [mm]. See the figure in step 1.
Frame
A
B
C
D
E
F
G
MR4
15
35
10
20
7
35
*
MR5
20
40
10
30
10
40
*
MR6
20
90
15
60
15
60
*
MR7
20
80
20
80
20
80
*
POWER CABLING
VACON · 69
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
5