NOTE!
The currents in given ambient temperatures (in chapter 10.2 Vacon® 100 HVAC -
technical data) are achieved only when the switching frequency is equal to or less
than the factory default.
10.1.2
MAINS VOLTAGE 380-500 V
Table 51: The power ratings of Vacon
®
100 HVAC in mains voltage 380-500 V, 50-60 Hz, 3~
Frame
Drive type
Loadability
Motor shaft power
Low*
400 V mains
480 V mains
Continuous
current I
L
[A]
Input current
I
in
[A]
10% overload
current [A]
10% overload
40°C [kW]
10% overload
40°C [Hp]
MR4
0003
3.4
3.4
3.7
1.1
1.5
0004
4.8
4.6
5.3
1.5
2.0
0005
5.6
5.4
6.2
2.2
3.0
0008
8.0
8.1
8.8
3.0
5.0
0009
9.6
9.3
10.6
4.0
5.0
0012
12.0
11.3
13.2
5.5
7.5
MR5
0016
16.0
15.4
17.6
7.5
10.0
0023
23.0
21.3
25.3
11.0
15.0
0031
31.0
28.4
34.1
15.0
20.0
MR6
0038
38.0
36.7
41.8
18.5
25.0
0046
46.0
43.6
50.6
22.0
30.0
0061
61.0
58.2
67.1
30.0
40.0
MR7
0072
72.0
67.5
79.2
37.0
50.0
0087
87.0
85.3
95.7
45.0
60.0
0105
105.0
100.6
115.5
55.0
75.0
MR8
0140
140.0
139.4
154.0
75.0
100.0
0170
170.0
166.5
187.0
90.0
125.0
0205
205.0
199.6
225.5
110.0
150.0
MR9
0261
261.0
258.0
287.1
132.0
200.0
0310
310.0
303.0
341.0
160.0
250.0
See 10.1.3 Overload capability.
TECHNICAL DATA, VACON® 100 HVAC