NOTE!
The currents in given ambient temperatures (in chapter 8.2 Vacon® 100 - technical
data) are achieved only when the switching frequency is equal to or less than the
factory default.
If your process includes a cyclical load, for example if there are lifts or winches, speak to the
manufacturer to get the dimensioning information.
8.1.3
MAINS VOLTAGE 525-600 V
Table 36: The power ratings of Vacon
®
100 in mains voltage 525-600 V, 50-60 Hz, 3~
Frame
Drive
type
Loadability
Motor shaft
power
Low
High
Max
current
I
s
2s
600 V
Continu
ous
current
I
L
[A]
Input
current
I
in
[A]
10%
over-
load
current
[A]
Continu
ous
current
I
H
[A]
Input
current
I
in
[A]
50%
over-
load
current
[A]
10%
over-
load
40
◦
C
[Hp]
50%
over-
load
50
◦
C
[Hp]
MR5
0004
3.9
4.6
4.3
2.7
3.2
4.1
5.4
3.0
2.0
0006
6.1
6.8
6.7
3.9
4.5
5.9
7.8
5.0
3.0
0009
9.0
9.0
9.9
6.1
6.7
9.2
12.2
7.5
5.0
0011
11.0
10.5
12.1
9.0
8.9
13.5
18.0
10.0
7.5
MR6
0018
18.0
19.9
19.8
13.5
15.2
20.3
27.0
15.0
10.0
0022
22.0
23.3
24.2
18.0
19.8
27.0
36.0
20.0
15.0
0027
27.0
27.2
29.7
22.0
23.1
33.0
44.0
25.0
20.0
0034
34.0
32.8
37.4
27.0
27.0
40.5
54.0
30.0
25.0
MR7
0041
41.0
45.3
45.1
34.0
38.4
51.0
68.0
40.0
30.0
0052
52.0
53.8
57.2
41.0
44.9
61.5
82.0
50.0
40.0
0062
62.0
62.2
68.2
52.0
53.2
78.0
104.0
60.0
50.0
MR8
0080
80.0
90.0
88.0
62.0
72.0
93.0
124.0
75.0
60.0
0100
100.0
106.0
110.0
80.0
89.0
120.0
160.0
100.0
75.0
0125
125.0
127.0
137.5
100.0
104.0
150.0
200.0
125.0
100.0
MR9
0144
144.0
156.0
158.4
125.0
140.0
187.5
250.0
150.0
125.0
0208
208.0
212.0
228.8
170.0
177.0
255.0
340.0
200.0
150.0
TECHNICAL DATA, VACON® 100
VACON · 121
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]