8.2 Troubleshooting Ex protective housing
DANGER
Loss of protective function!
•
After several short-circuits / ignitions in the protective cabinet, the protective
function cannot be ensured anymore!
•
After resetting/replacing the thermal fuse in the process gas analyser, check
the device for proper function!
•
In case of housing damage (protective housing, terminal boxes), check their
protective functions and replace!
Replace the flame arresters!
•
After fire or explosion at the flame arrester.
•
Visible mechanical damage at housing, lid or retaining ring of flame arrester.
•
Strong soiling or corrosion of the fire protection.