Operating
Software diagnostic messages
134
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
VAUX1/VAUX2 diagnostics
(slot 1, according ot configuration tool)
PROFINET Diagnostics
Overcurrent VAUX1 (pin 1) at C0, channel 0/1
0x01D0
0
Overcurrent VAUX1 (pin 1) at C1, channel 2/3
0x01D1
Overcurrent VAUX1 (pin 1) at C2, channel 4/5
0x01D2
Overcurrent VAUX1 (pin 1) at C3, channel 6/7
0x01D3
Overcurrent VAUX1 (pin 1) at C4, channel 8
0x01E8
Overcurrent VAUX1 (pin 1) at C5, channel 10
0x01EA
Overcurrent VAUX1 (pin 1) at C6, channel 12
0x01EC
Overcurrent VAUX1 (pin 1) at C7, channel 14
0x01EE
Overcurrent VAUX2 (pin 2) at C4, channel 9
0x01F9
Overcurrent VAUX2 (pin 2) at C5, channel 12
0x01FB
Overcurrent VAUX2 (pin 2) at C6, channel 14
0x01FD
Overcurrent VAUX2 (pin 2) at C7, channel 9
0x01FF
IO-Link port diagnostics
PROFINET Diagnostics
IO-Link port 1
(Slot 2, according to configuration tool)
Connector
Error code
Channel
Undervoltage (VLOW)
C0
0x0002
0
Overcurrent (VHIGH)
0x0003
Overload (OVL)
0x0004
Over temperature (OTMP)
0x0005
Wrong or missing device (CFGER)
0x0006
Upper limit value exceeded (ULVE)
0x0007
Lower limit value underrun (LLVU)
0x0008
Data storage error (DSER)
0x0009
Process input data invalid (PDINV)
Maintenance events (EVT1)
Out of specification error (EVT2)
Port parameterization error (PPE)
Parameterization error (PRMER)
0x0010
Hardware error (HWER)
0x0010
IO-Link port 2
(Slot 3, according to configuration tool)
Similar to port 1
C1
2
IO-Link port 3
(Slot 4, according to configuration tool)
Similar to port 1
C2
4
IO-Link port 4
(Slot 5, according to configuration tool)
Similar to port 1
C3
6
IO-Link port 5
(Slot 6, according to configuration tool)
Similar to port 1
C4
8
IO-Link port 6
(Slot 7, according to configuration tool)