Commissioning
Commissioning the device in EtherNet/IP™
82
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Instance 125 – 8 byte IN/8 byte OUT
The description of the input data can be found in chapter “Operating” [
Word
no.
Bit no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Status word
0x00
-
FCE
-
-
-
-
V1
-
V2
-
-
-
-
-
-
Diag
Inputs
0x01
-
DI14
(SIO)
-
DI12
(SIO)
-
DI10
(SIO)
-
DI8
(SIO)
DXP7 DI6
(SIO)
DXP5 DI4
(SIO)
DXP3 DI2
(SIO)
DXP1 DI0
(SIO)
Process input data valid
0x02
-
DVS
14
-
DVS
12
-
DVS
10
-
DVS8 -
DVS6 -
DVS4 -
DVS2 -
DVS0
IO-Link process input data
0x03…
0x06
4 words per port
…
0x1F…
0x22
Output assembly instances
EtherNet/IP™
Connection
Output Assembly
Control word
[byte]
DXP outputs
[byte]
IO-Link out-
puts [byte]
VAUX [byte]
Instance
Size [8 bit]
Exclusive
Owner
104
262
2
2
256
2
IOL 4 IN/4
OUT
150
38
2
2
32
2
IOL 6 IN/6
OUT
151
54
2
2
48
2
IOL 8 IN/8
OUT
152
70
2
2
64
2
Instance 104 – Exclusive Owner
The description of the output data can be found in chapter “Operating” [
Word
no.
Bit no.
15
14
13
12
11 10 9 8 7
6
5
4
3
2
1
0
Control Word
0x00
-
reserved
DXP outputs
0x01
-
-
-
-
-
-
-
-
DXP7 -
DXP5 -
DXP3
-
DXP1
-
IO-Link process output data
0x02…
0x11
16 words per port
…
0x72…
0x81