Commissioning
Commissioning the device in PROFINET
38
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Acyclic device user data
Index
Name
Data type
Access
Comment
Dec.
Hex.
1
0x01
Module paramet-
ers
WORD
read/
write
Parameter data of the module
(slot 0)
2
0x02
Module designa-
tion
STRING
read
Designation assigned to the
module (slot 0)
3
0x03
Module revision
STRING
read
Firmware revision of the module
4
0x04
Vendor ID
WORD
read
Ident no. Turck
5
0x05
Module name
STRING
read
The device name assigned to
the module
6
0x06
Module type
STRING
read
Device type of the module
7
0x07
Device ID
WORD
read
Ident no. of the module
8…23
0x08…
0x17
reserved
-
-
-
24
0x18
Module dia-
gnostics
WORD
read
Diagnostic data of the module
(slot 0).
25…31 0x19…
0x1F
reserved
-
-
-
32
0x20
Input list
ARRAY of
BYTE
read
List of all module input channels
33
0x21
Output list
ARRAY of
BYTE
read
List of all module output chan-
nels
34
0x22
Diag. list
ARRAY of
BYTE
read
List of all I/O-channel dia-
gnostics
35
0x23
Parameter list
ARRAY of
BYTE
read
List of all I/O-channel paramet-
ers
36…
28671
0x24…
0x6FFF
reserved
-
-
-
28672
0x7000 Module paramet-
ers
WORD
read/
write
Activate field bus protocol
28673…
45039
0x7001
…
0xAFEF
reserved
-
-
-
45040
0xAFF0 I&M0-functions
read
Identification & Maintaining
45041
0xAFF1 I&M0-functions
STRING[54]
read/
write
I&M Tag function and
location
45042
0xAFF2 I&M2-functions
STRING[16]
read/
write
I&M Installation Date
45043
0xAFF3 I&M3-functions
STRING[54]
read/
write
I&M Description Text
45044
0xAFF4 I&M4-functions
STRING[54]
read/
write
I&M Signature
45045…
45055
0xAFF5
…
0xAFFF
I&M5 to I&M15-
functions
-
not supported