Commissioning
Commissioning the device in Modbus TCP
64
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Register 0x113E and 0x113F: Save Modbus-Connection-Parameters
Registers 0x113E and 0x113F are used for the non-volatile saving of parameters in registers
0x1120 and 0x1130 to 0x113B.
Procedure:
Write 0x7361 to register 0×113E.
Write 0x7665 ("save") within 30 seconds in register 0x113F to activate the reset of the re-
gisters. Both registers can also be written with one single request using the function
codes FC16 and FC23.
a
The parameters are saved.
8.8.3
Data width
Module
Process input data
Process output data
Alignment
TBEN-L…-8IOL
344 byte
260
word by word