V02.00 | 2019/10
121
9.2.1
Port functions for Port 0 (IO-Link Master)
IO-Link Index (port function invocation)
The access to the IO-Link master functionalities (port 0) is done via index 65535:
Subindex 64: Master Port Validation Configuration
The object writes a specific configuration of the Devices to be connected to the IO-Link port to
the Master. The master stores the data for the The IO-Link device expected at the port and then
accepts only one device at the port with exactly matching data (vendor ID, device ID and serial
number).
The Master Port Validation Configuration is only useful in combination with an operation mode
with validation (
IO-Link with family compatible device
,
IO-Link with compatible device
,
IO-
Link with identical device
.
Entity_Port
IO-Link sub index
Read/write
Length
0
64
Write
Max. 192 byte
Structure of the command IOL_Port_Config:
Content
Size
Format
Comment
IOL1
VENDOR_ID
2 byte
Unsigned 16
DEVICE_ID
4 byte
Unsigned 32
FUNCTION_ID
2 byte
Unsigned 16 Value: 0
SERIAL_NUMBER
16 byte
String
IOL2
VENDOR_ID
2 byte
Unsigned 16
DEVICE_ID
4 byte
Unsigned 32
FUNCTION_ID
2 byte
Unsigned 16 Value: 0
SERIAL_NUMBER
16 byte
String
IOL3
VENDOR_ID
2 byte
Unsigned 16
DEVICE_ID
4 byte
Unsigned 32
FUNCTION_ID
2 byte
Unsigned 16 Value: 0
SERIAL_NUMBER
16 byte
String
IOL4
VENDOR_ID
2 byte
Unsigned 16
DEVICE_ID
4 byte
Unsigned 32
FUNCTION_ID
2 byte
Unsigned 16 Value: 0
SERIAL_NUMBER
16 byte
String
IOL5
VENDOR_ID
2 byte
Unsigned 16
DEVICE_ID
4 byte
Unsigned 32
FUNCTION_ID
2 byte
Unsigned 16 Value: 0
SERIAL_NUMBER
16 byte
String
IOL6
VENDOR_ID
2 byte
Unsigned 16
DEVICE_ID
4 byte
Unsigned 32
FUNCTION_ID
2 byte
Unsigned 16 Value: 0
SERIAL_NUMBER
16 byte
String