V02.00 | 2019/10
139
11
Troubleshooting
If the device does not work as expected, proceed as follows:
Exclude environmental disturbances.
Check the connections of the device for errors.
Check device for parameterization errors.
If the malfunction persists, the device is faulty. In this case, decommission the device and re-
place it with a new device of the same type.
11.1
Eliminate parameterization errors
DXP channels
Error
Possible causes:
Remedy
DXP output
does not switch
The output is deactivated per default.
Switch on the output via parameter
Activate output
(DXP_EN_DO =1).
IO-Link channels
LED
behavior
Diagnostics
Possible causes:
Remedy
DIA and IOL
flash red
Data storage error IO-Link device according to
IO-Link V1.0 connected IO-
Link devices in accordance
with IO-Link specification
V1.0 do not support data stor-
age.
Set parameter Data storage mode to
deactivated, clear
.
a
Data storage remain deactivated.
The data storage buffer con-
tains data of another device.
Set parameter Data storage mode to
deactivated, clear
.
Re-activate the data storage if neces-
sary.
Wrong or missing
device
The connected device does
not match the configured
one (wrong vendor-ID,
device-ID etc.)
Adapt the parameterization of the
IO-Link port (Vendor ID, Device ID,
etc.) at the master.
The parameterization can be done
manually via DTM, the web server or
similar or by teaching the master us-
ing the IO-Link Call (port 0 function,
sub index 67: Teach mode).
Evaluating Process
Input Data
Certain IO-Link devices send a
process input data invalid
diagnosis if the process value
cannot be measured.
Deactivate the sending of the dia-
gnosis for the IO-Link port with the
parameter
Process input data in-
valid
Ò
No diagnostic generated.