Parameterizing and Configuring
Parameters
114
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Word no.
Bit no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
IO-Link port 8
0x3A…
0x41
Assignment similar to IO-Link port 1 (Word 0x02...0x09)
VAUX monitoring
0x42
-
-
-
-
-
-
VAUX1 pin1
C1 (ch2/3)
-
-
-
-
-
-
VAUX1 pin1
C0 (ch0/1)
0x43
-
-
-
-
-
-
VAUX1 pin1
C3 (ch6/7)
-
-
-
-
-
-
VAUX1 pin1
C2 (ch4/5)
0x44
-
-
-
-
-
-
VAUX1 pin1
C5 (ch10)
-
-
-
-
-
-
VAUX1 pin1
C4 (ch8)
0x45
-
-
-
-
-
-
VAUX1 pin1
C7 (ch14)
-
-
-
-
-
-
VAUX1 pin1
C6 (ch12)
0x46…
0x47
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0x48
-
-
-
-
-
-
VAUX2 pin2
C5 (ch11)
-
-
-
-
-
-
VAUX2 pin2
C4 (ch9)
0x49
-
-
-
-
-
-
VAUX2 pin2
C7 (ch15)
-
-
-
-
-
-
VAUX2 pin2
C6 (ch13)
The default values are shown in
bold
type.
Parameter name
Value
Meaning
Description
dec.
Hex.
Manual output re-
set after overcur-
rent
(DXPx_SRO)
0
0x00 Yes
The output switches on automatically after an over-
load.
1
0x01 No
The output is manually switched-off after an overload
until a new set-command is given (rise and fall).
Activate output
Chx (DXPx_ENDO)
0
0x00 Yes
The output at pin 2 is deactivated.
1
0x01 No
The output at pin 2 is activated.
Operation mode
0
0x00 IO-Link without valida-
tion
Pin 4 is operated in IO-Link mode.
The master does not check if the connected device
matches the configured one.
1
0x01 IO-Link with compatible
device
Pin 4 is operated in IO-Link mode.
The master checks if the Vendor ID and the MSB of
the Device ID (this byte defines the product family) of
the connected device match those of the configured
one. If the master detects a mismatch, the IO-Link
communication is established, but there is no process
data exchange. The device remains in the safe state
(Pre-Operate).
Parameters and diagnostic information can be read
and respectively written.