Commissioning
Commissioning an IO-Link device with IO-Link V1.1
32
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
8.4
Commissioning an IO-Link device with IO-Link V1.1
The data storage of the master should be cleared before a device with a different device type is
connected to an IO-Link port which has already been used before.
The data storage memory of the master can be deleted in two ways:
n
Set back the master to factory settings.
n
The data storage memory is deleted using the parameter
Data storage mode
.
Setting back the master to factory settings with the DTM
From the
Factory settings
drop-down menu, select
Set to factory settings
.
Load the parameter changes into the device.
a
The DTM resets the device automatically.
Fig. 31: Example: Reset device to factory settings via DTM
Connect the IO-Link V1.1 device.
a
The LED IOL at the IO-Link port is green, IO-Link communication active.