SS-SVX11K-EN
81
Figure 55.
Q667 switching subbase & T7067 thermostat terminal identification
Switching Subbase
(Honeywell Q667)
Electronic Thermostat
(Honeywell T7067)
Terminal Layout
Internal Wiring Schematic
1 = Common (- DC) and
Night Setback/Setup Input
2 = +20 VDC Input
3 = Duct Sensor Input
4 = COOL Signal Output
5 = HEAT Signal Output
6 = Heating Setback
7 = Not Used
8 = Night Setup of Cooling
Setpoint
9 = Fan Switching
10 = Fan Switching
Wiring Terminal Identification:
1 = Common (- DC) and
Night Setback/Setup Input
2 = +20 VDC Input
3 = Duct Sensor Input
4 = COOL Signal Output
5 = HEAT Signal Output
6 = Heating Setback
7 = Not Used
8 = Night Setup of Cooling
Setpoint
Wiring Terminal Identification:
RAUC\Thermostat Terminal ID
System
7
6
5
4
1
2
3
8
7
6
9
4
1
2
3
8
10
5
OFF
HEAT
AUTO
COOL
OFF
HEAT
AUTO
COOL
OFF
HEAT
COOL
AUTO
ON
FAN
AUTO
System
Fan
AUTO
ON
COOL
AUTO
HEAT
ON
7
6
9
4
1
2
3
8
10
5
Table 26.
(Q667) switching subbase
Subbase
Switch
Positions
Check Continuity
between These Terminal
Pairs
Circuit
should
be
Fan
System
ON
N/A
9 (Subbase) & 10 (Subbase)
Closed
AU-
TO
OFF
9 (Subbase) & 10 (Subbase)
Open
5 (Subbase) & 5 (T’stat)
Open
4 (Subbase) & 4(T’Stat)
Open
AU-
TO
HEAT
9 (Subbase) & 10 (Subbase)
Open
5 (Subbase) & 5 (T’stat)
Closed
4 (Subbase) & 4(T’Stat)
Open
AU-
TO
AUTO
9 (Subbase) & 10 (Subbase)
Closed
5 (Subbase) & 5 (T’stat)
Closed
4 (Subbase) & 4(T’Stat)
Closed
AU-
TO
COOL
9 (Subbase) & 10 (Subbase)
Closed
5 (Subbase) & 5 (T’stat)
Open
4 (Subbase) & 4(T’Stat)
Closed
Thermostat Checkout
Once the subbase is mounted, before connecting any
wiring, use an ohm meter and complete the continuity
checks listed in .
Thermostat Wiring
W
WA
AR
RN
NIIN
NG
G
H
Ha
azza
arrd
do
ou
uss V
Vo
olltta
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d.. V
Ve
erriiffy
y tth
ha
att n
no
o
p
po
ow
we
err iiss p
prre
esse
en
ntt w
wiitth
h a
a v
vo
ollttm
me
ette
err..
Before installing any connecting wiring, see drawings
in the Dimensions and Weights chapter for the
electrical access locations provided on the unit. Wire
the thermostat in accordance with field connection
diagram, numbers 2307-9122 (for 20 to 60 ton units)
and 2307-9144 (for 80 to 120 ton units).
Discharge Air Sensor (Honeywell 6RT1)
A discharge air sensor ships with each unit when the
constant volume control option is ordered. The sensor
should be installed in a turbulent free area of the
discharge air duct at a location that will provide
accurate supply air sensing. Refer to the illustration in
for installation and sensor dimensional
information.