62
SS-SVX11K-EN
Table
18.
RAUJ
electrical
data
(continued)
Unit
Size
(ton)
Rated
Voltage
(a)
Condenser
Fan
Motor
(b)
Compressor
Motor
Unit
Characteristics
CPT
Amps
RLA
LRA
Qty
FLA
Qty
1A/2A
1B/2B
1C/2C
1A/2A
1B/2B
1C/2C
MCA
(c)
MOP
(d)
60
200/60/3XL
6
4.1
3
4
56.9
56.9
-
351
351
-
270
300
230/60/3XL
6
4.1
2
4
48.8
48.8
-
351
351
-
234
250
460/60/3XL
6
1.8
1
4
25.5
25.5
-
197
197
-
121
125
575/60/3XL
6
1.4
1
4
23.1
23.1
-
146
146
-
108
125
380/415/50/3XL
6
1.7
1
4
25.4
25.4
-
197
197
-
119
125
80
200/60/3XL
8
4.1
4
6
60.5
60.5
60.5
320
320
320
415
450
230/60/3XL
8
4.1
3
6
52
52
52
320
320
320
361
400
460/60/3XL
8
1.8
2
6
25.4
25.4
25.4
160
160
160
176
200
575/60/3XL
8
1.4
1
6
20.3
20.3
20.3
135
135
135
140
150
100
200/60/3XL
12
4.1
4
6
60.5
60.5
83.9
320
320
485
484
500
230/60/3XL
12
4.1
3
6
52
52
74.5
320
320
485
428
500
460/60/3XL
12
1.8
2
6
25.4
25.4
37.2
160
160
215
209
225
575/60/3XL
12
1.4
1
6
20.3
20.3
29.8
135
135
175
167
175
120
200/60/3XL
12
4.1
4
6
83.9
83.9
83.9
485
485
485
578
600
230/60/3XL
12
4.1
3
6
74.5
74.5
74.5
485
485
485
518
600
460/60/3XL
12
1.8
2
6
37.2
37.2
37.2
215
215
215
257
300
575/60/3XL
12
1.4
1
6
29.8
29.8
29.8
175
175
175
205
225
(a)
V
oltage
Utilization
Ra
nge
is
+/-
10%
of
Rated
voltage
(use
range):
200/60/3
(180-220),
230/60/3
(208-254),
460/60/3
(414-506),
575/60/3
(516-633),
380/50/3
(342-418),
415/50/3
(373-456)
(b)
Electrical
information
is
for
each
individual
motor
.
(c)
Minimum
circuit
ampacity
(MCA)
is
125
percent
of
the
RLA
of
one
compressor
motor
plus
the
total
RLA
of
the
remaining
motors.
(d)
Maximum
Overcurrent
Protection
Device
permitted
by
NEC
440-22
is
225
percent
of
the
RLA
of
one
compressor
motor
plus
the
total
RLA
of
the
remaining
motors.