1. Turn the control circuit switch 1S2, in the unit
control panel, to the “OFF” position.
2. At the Master Energy Controller, disconnect wire
connected to Terminal T1. Use a digital ohmmeter
to measure resistance between Terminal T and the
wire removed from Terminal T1.
3. Use chart in
to convert the
measured resistance to an equivalent temperature.
4. Measure the actual temperature at the sensor
location. If the measured resistance in step 2 is not
within ± 10.0 ohms of the actual temperature, the
6RT1 is out of range; replace it.
N
No
otte
e:: Before condemning the sensor, verify that
the connecting cable resistance is not
excessive. Refer to the “Field Installed
Control Wiring” section.
5. Make all necessary repairs and reconnect the duct
sensor lead to terminal T1 on the controller.
6. Turn switches 1S2, 5S1, & 5S2 to the “ON” position
to restore power to the control system.
Figure 72.
6RT1 discharge duct sensor “temperature vs resistance” curve