Table 43.
Compressor circuit breakers (200-230 volts) (continued)
Must Hold
Must Trip
Unit
Voltage
1A / 2A
1B / 2B
1C / 2C
1A / 2A
1B / 2B
1C / 2C
50 Ton
200
57.1
63.1
-
65.7
72.5
-
230
51.4
57.1
-
59.2
65.7
-
60 Ton
200
69.3
69.3
-
79.7
79.7
-
230
59.4
59.4
-
68.3
68.3
-
80 Ton
200
73.7
73.7
73.7
84.7
84.7
84.7
230
63.1
63.1
63.1
72.5
72.5
72.5
100 Ton
200
73.7
73.7
105.2
84.7
84.7
121
230
63.1
63.1
90.7
72.5
72.5
104.3
120 Ton
200
105
105.2
105.2
121
121
121
230
90.7
90.7
90.7
104.3
104.3
104.3
Table 44.
Compressor circuit breakers (460-575 volts)
Dial Setting
Unit
Voltage
1A / 2A
1B / 2B
1C / 2C
20 Ton
460
20.8
20.8
-
575
17.7
17.7
-
25 Ton
460
20.8
24.9
-
575
17.7
21.4
-
30 Ton
460
28.5
28.5
-
575
25.9
25.9
-
40 Ton
460
20.8
20.8
-
575
17.7
17.7
-
50 Ton
460
22.6
24.9
-
575
19.1
21.4
-
60 Ton
460
28.5
28.5
-
575
25.9
25.9
-
80 Ton
460
28.4
28.4
28.4
575
22.7
22.7
22.7
100 Ton
460
28.4
28.4
41.6
575
22.7
22.7
33.3
120 Ton
460
41.6
41.6
41.6
575
33.3
33.3
33.3