116
SS-SVX11K-EN
Figure 82.
100 Ton cooling cycle pressure curve
105°F OD
95°F OD
85°F OD
75°F OD
65°F OD
Suction pressure, PSIG
95
105
115
125
135
145
250
300
350
400
450
500
550
Dischar
ge pr
essure
, PS
IG
100T Cooling Cycle Pressure Curve
All compressors and condenser fans running
Figure 83.
120 Ton cooling cycle pressure curve
105°F OD
95°F OD
85°F OD
75°F OD
65°F OD
Suction pressure, PSIG
95
105
115
125
135
145
250
300
350
400
450
500
550
Discha
rge
pressur
e,
PSIG
120T Cooling Cycle Pressure Curve
All compressors and condenser fans running
Final System Setup
W
WA
AR
RN
NIIN
NG
G
H
Ha
azza
arrd
do
ou
uss V
Vo
olltta
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d.. V
Ve
erriiffy
y tth
ha
att n
no
o
p
po
ow
we
err iiss p
prre
esse
en
ntt w
wiitth
h a
a v
vo
ollttm
me
ette
err..
After completing the Pre-start and Start-up procedures
outlined in the previous sections, perform these final
checks before leaving the unit:
•
Turn the 115 volt control circuit switch 1S2 “Off”
and program the Night Setback (NSB) panel (if
applicable) for proper unoccupied operation. Refer
to the programming instructions for the specific
panel.
•
Verify “System” selection switch and the “Fan
Mode” selection switch at the Remote panel is set
correctly.
•
Verify that the “System” control switch for the
supply fan is “On”.
•
Verify that the “System” control switch for the
supply fan or the chilled water pump is “On.”
•
Set the correct “Operating Temperature” for the
system at the system controller. Refer to Minimum
Starting Ambient Temperature table for the
recommended control set points for the appropriate
control option.
•
Turn the 115 volt control circuit switch 1S2 “On”.
The system will start automatically once a request
for cooling has been given.
•
Verify that all exterior panels and the control panel
doors are secured in place.
Table 38.
Recommended operating setpoints, 20 to 120 ton units
Control
Control Setting
Recommended Setting
Discharge Air Controller
(VAV units only)
Supply Air Setpoint
Set at design discharge (supply) air temperature; minimum setting = 55° F
Reset Setpoint
Set at maximum amount of allowable reset for supply air setpoint.
Control Band
Set at 6°F Minimum Setpoint
Chiller Control
(EVP units only)
Freezestat
Leaving Fluid Setpoint
Set at design leaving chilled water temperature (typically) 44° F
Reset Setpoint
Set at maximum amount of allowable reset for leaving fluid setpoint.
Control Band
Set at 6° F Minimum Setpoint (minimum control temperature cannot be
lower than freezestat setting)
Freezestat
Low Limit Solution
Temperature
Set at 5° F Minimum above the Chilled Solution Freeze Temperature
Zone Thermostat
(CV units only)
Zone Setpoint
Set at desired space temperature.
Note:
For "No Controls" Units, see System Engineer