SS-SVX11K-EN
43
Unit Mounting
Figure 30.
Mounting location
Control
Panel
80-120 Ton
1
2
3
4
5
6
7
8
Y
X
Control
Panel
Control
Panel
20-30 Ton
40-60 Ton
1
1
2
2
3
3
4
4
5
6
Y
Y
X
X
Table 7. Isolator mounting locations (in)
Unit Size
(tons)
Mounting Location
1
2
3
4
5
6
7
8
20/25/30
X
8.00
8.00
80.125
80.125
-
-
-
-
Y
58.75
1.25
58.75
1.25
-
-
-
-
40
X
8.00
8.00
44.125
44.125
80.25
80.25
-
-
Y
87.125
1.25
87.125
1.25
87.125
1.25
-
-
50/60
X
8.00
8.00
56.875
56.875
105.75
105.75
-
-
Y
87.125
1.25
87.125
1.25
87.125
1.25
-
-
80
X
8.00
8.00
80.125
80.125
108.125
108.125
168.25
168.25
Y
87.125
1.25
87.125
1.25
87.125
1.25
87.125
1.25
100/120
X
8.00
8.00
105.625
105.625
121.625
121.625
219.25
219.25
Y
87.125
1.25
87.125
1.25
87.125
1.25
87.125
1.25
Table 8. RAUJ point loading weights (lbs)
Unit
Size
(tons)
Mounting Location
1
2
3
4
5
6
7
8
20
475.5
383.3
403.2
311.0
—
—
—
—
25
491.2
399.3
412.2
320.3
—
—
—
—
30
491.2
399.3
412.2
320.3
—
—
—
—
40
452.3
415.7
440.3
403.7
428.3
391.8
—
—
50
365.5
331.0
427.8
393.3
700.1
650.3
—
—
60
367.2
332.8
426.0
391.6
692.5
642.9
—
—
80
798.3
462.1
786.7
450.5
785.1
448.9
772.4
436.1
100
871.1
609.5
881.0
616.2
882.6
432.1
892.5
436.8
120
988.2
614.7
948.3
587.4
941.8
583.0
901.8
555.8