25
System Programming SETUP
Used on Units:
All Units with GBAS5V,
GBAS10V or TCI
Possible Values:
None - All Units
1. Press the + or - key until the proper value is displayed.
25% - 2 Ckt Only
2. Press the ENTER key to confirm this choice.
50% - All Units
3. Press the NEXT key until the following screen is displayed.
75% - 2 Ckt Only
100% - All Units
Used on Units:
All Units
Possible Values:
Enabled, Disabled
OR
Note:
Lead\Lag can not be Enabled if Hot Gas
Bypass is Enabled.
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
With Hot Gas Bypass Option
installed
Possible Values:
Enabled, Disabled
1. Press the + or - key until the proper value is displayed.
Note:
Hot Gas Bypass can not be Enabled if
2. Press the ENTER key to confirm this choice.
Lead\Lag is Enabled.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
With Hot Gas Bypass Option installed
Possible Values:
10 to 120 minutes
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
10 to 120 minutes
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
50% Capacity per ckt
(Auto Reset Diag)
1. Press the + or - key until the proper value is displayed.
Allow normal operation
2. Press the ENTER key to confirm this choice.
(Info Reset Diag)
3. Press the NEXT key until the following screen is displayed.
Shut off compressors
(Manual Reset Diag)
Used on Units:
All Units
Possible Values:
Enable, Disable
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
On, Auto
OR
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
Demand Limit Definition: NONE
Reduce cooling capacity by this amount
Compressor Lead/Lag Function: DISABLED
Stage Comp(s) Up/Down in Fixed Sequence
Capacity=50% if LST exceeds Hot Strt STP
During Hot Start Time Interval: 60 Min
Hot Operation Response Option:
50% CAPACITY PER CKT, AUTO RESET DIAG
Pumpdown Function: DISABLED
Default Chiller Solution Pump Mode: ON
Pump Always ON Except for Emergency STOP
Hot Gas Bypass Function: DISABLED
Provides Cooling Level Less Than Cool 1
Hot Gas Bypass Max Run Time 30 Min
Max HGBP Duration Until Shut Off Comp
Compressor Lead/Lag Function: ENABLED
1st On = Least Starts, 1st Off = Most Runtime
Default Chiller Solution Pump Mode: AUTO
Turn Pump ON As Requested By CGM Module