35
SETPOINTS Menu
The SETPOINTS menu is used to designate default
setpoints, low ambient compressor lockout setpoints and
select setpoint sources.
These setpoints will be active (in use) for the "Setpoint
Source Selection" designated as "DEFAULT" for these in-
puts.
System Programming SETPOINTS
When a setpoint screen is displayed for 30 minutes without
a key being pressed, the LCD screen will revert to the gen-
eral operating status display. If this happens, press the
SETPOINT key again to return to the setpoint menu.
Used on Units:
All Units
Possible Values:
Based on Configured Leaving Solution STP Range:
Range 51.0 - 65.0°F
1. Press the + or - key until the proper value is displayed.
Range 40.0 - 50.0°F
2. Press the ENTER key to confirm this choice.
Range 30.0 - 39.0°F
3. Press the NEXT key until the following screen is displayed.
Range 20.0 - 29.0°F
Range 10.0 - 75.0°F (SPECIAL)
Used on Units:
Units with Ice Building Control Option
Possible Values:
20.0 to 31.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
-10.0 to 60.0 F
Note: Maximum setting may be limited by ’Hi Leaving
1. Press the + or - key until the proper value is displayed.
Solution Setpoint’
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Brazed Plate Units
Possible Values:
0 to 45.0 F
Note: Maximum setting may be limited by ’Hi Leaving
1. Press the + or - key until the proper value is displayed.
Solution Setpoint’
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
60.0 to 80.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
-20.0 to 50.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
-20.0 to 60.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
Human Interface STP Menu
GBAS 0-5VDC Module
1. Press the + or - key until the proper value is displayed.
GBAS 0-10VDC Module
2. Press the ENTER key to confirm this choice.
Ext Leaving Soln STP Input
Stop Ice Making When Ent Soln Temp Below
Hi Ice Build Terminate Setpoint: 27.0 F
Comp(s) OFF if Solution Temp Below
Low Solution Cutout Temp: 35.0 F
HI Hot Start Load Limit Setpoint: 71.0 F
Request Pump ON When OA Temp Less Than
Low Ambient Pump Override Temp: 35 F
Low Ambient Comp Lockout Temp: 40 F
Comp(s) OFF if OA Temp Below This Value
Use Leaving Solution Setpoint
From: HUMAN INTERFACE STP MENU
Heat Output ON When EST or LST Less Than
Heat Tape Temperature Setpoint: 40.0 F
HI Leaving Solution Setpoint: 44 F