21
System Operating Status
Used on Units:
40-60 Ton with Superheat/Subcooling
Module installed
Possible Values:
-40.0 to 200 F
1. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
-40.0 to 200 F
1. Press the NEXT key until the following screen is displayed.
Used on Units:
With TCI Module Installed
Possible Values:
-40.0 to 200 F
1. Press the NEXT key until the following screen is displayed.
2. Pressing the NEXT key will display the beginning of
the Submenu.
3. Press the NEXT key again to advance to the following screen.
Refrigerant Ckt 2 - Temperature Data
Suction 72.0 F Sat Liquid 97.0 F
Temp Measured By Sensor Connected To
CGM Zone Temp Input 75.0 F
Temp Measured By Sensor Connected To
CGM ICS Temp Input 62.0 F
End of Submenu (NEXT) to Re-enter STATUS
Used on Units:
With Ice Building Control Option
Possible Values:
Off, Make Ice
1. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
Flow, No Flow
1. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units with Superheat/Subcooling
Possible Values:
Suction = 0.0 to 100.0 PSIG
Liquid = 0.0 to 400.0 PSIG
Comp Off
1. Press the NEXT key until the following screen is displayed.
Used on Units:
40 - 60 Ton Units with Superheat/Cooling
Possible Values:
Suction = 0.0 to 100.0 PSIG
Liquid = 0.0 to 400.0 PSIG
Comp Off
1. Press the NEXT key until the following screen is displayed.
Used on Units: With
Current Sensing Module
Possible Values:
0 to 255
1. Press the NEXT key until the following screen is displayed.
Used on Units: With
Current Sensing Module
Possible Values:
0 to 255
CGM Ice Build Command Input: OFF
CGM Evap Soln Flow Switch Input: FLOW
Refrigerant Ckt 1 - Pressure Data
Suction 72 PSIG Liquid 265 PSIG
Refrigerant Ckt 2 - Pressure Data
Suction 65 PSIG Liquid 251 PSIG
Compressor 1A Phase Currents - Amps
Phase A 86 Phase B 84
Compressor 1B Phase Currents - Amps
Phase A 81 Phase C 78
1. Press the ENTER key until the following screen is displayed.
2. Press the NEXT key to bypass this menu and advance to
"GBAS 0-5VDC Module Status Submenu"
Misc Input Status Submenu
Press ENTER to View Data in This Submenu