General Information
Factory Presets (Continued)
Factory Preset
Changed
See page...
To adjust
To
to adjust
Press....
Ice Building Control Fuctions
Ice Building Function
Disabled
26
SETUP
Ice Building Mode
One Time
26
SETUP
Ice Rebuild Delay Time
360 Minutes
26
SETUP
GBAS 0-5 VDC Module I/O Assignments
GBAS (0-5 VDC) Analog Input 1 Assignment
Not Assigned
27
SETUP
GBAS (0-5 VDC) Analog Input 2 Assignment
Not Assigned
27
SETUP
GBAS (0-5 VDC) Analog Input 3 Assignment
Not Assigned
27
SETUP
GBAS (0-5 VDC) Analog Input 4 Assignment
Not Assigned
27
SETUP
GBAS (0-5 VDC) Binary Output 1 Definition
Indicate any comp
is running
28
SETUP
GBAS 0-5 V Output 1 Alarm Assignments
Any active diagnostic
28
SETUP
GBAS (0-5 VDC) Binary Output 2 Definition
Indicate selected
diagnostics
29
SETUP
GBAS 0-5 V Output 2 Alarm Assignments
Comp protection LPC
Open Ckt 1
29
SETUP
Comp protection LPC
Open Ckt 2 (40-60 Ton)
29
SETUP
Compressor Trip Ckt 1
29
SETUP
Compressor Trip Ckt 2
(40 - 60 Ton)
29
SETUP
Comp Contactor Fail Ckt 1
29
SETUP
Comp Contactor Fail Ckt 2
(40 - 60 Ton)
29
SETUP
Low Press Control
Open - Ckt 1
29
SETUP
Low Press Control
Open - Ckt 2 (40-60 Ton)
29
SETUP
GBAS (0-5 VDC) Binary Output 3 Definition
Indicate Unit at
Max capacity
29
SETUP
GBAS (0-5 VDC) Output 3 Alarm Assignments
Any active diagnostic
29
SETUP
GBAS (0-5 VDC) Binary Output 4 Definition
Indicate selected
diag alarms
29
SETUP
GBAS (0-5 VDC) Output 4 Alarm Assignments
Any active diagnostic
29
SETUP
GBAS (0-5 VDC) Binary Output 5 Definition
Indicate selected
diag alarms
29
SETUP
GBAS (0-5 VDC) Output 5 Alarm Assignments
Any active diagnostic
29
SETUP
GBAS 0-10 VDC Module I/O Assignments
GBAS (0-10 VDC) Analog Input 1 Assignment
Not Assigned
29
SETUP
GBAS (0-10 VDC) Analog Input 2 Assignment
Not Assigned
29
SETUP
GBAS (0-10 VDC) Analog Input 3 Assignment
Not Assigned
29
SETUP
GBAS (0-10 VDC) Analog Input 4 Assignment
Not Assigned
29
SETUP
GBAS (0-10 VDC) Binary Output Definition
Indicate selected
diag alarms
29
SETUP
GBAS (0-10 VDC) Output Alarm Assignments
Any active diagnostic
30
SETUP
GBAS (0-10 VDC) Analog Output 1 Assignment
Leaving solution temp
30
SETUP
GBAS (0-10 VDC) Analog Output 2 Assignment
Entering solution temp
30
SETUP
GBAS (0-10 VDC) Analog Output 3 Assignment
Active cooling capacity
30
SETUP
GBAS (0-10 VDC) Analog Output 4 Assignment
Outside air temperature
30
SETUP
CGM alarm output definitions
Any Active Diagnostic
30
SETUP
Summary of Contents for IntelliPak CGAF Series