General Information
Factory Presets
The CGM controlled unit has many operating functions
whose settings are preset at the factory, but may be modi-
fied to meet the unique requirements of each job. The fol-
lowing list identifies each of the unit's adjustable functions
and the value assigned to it. If these factory presets match
your application's requirements and the"System Start-Up
procedures in the Installation, Operation & Maintyenance
manual has been completed, simply press the AUTO key at
the Human Interface module to begin unit operation.
If your application requires different settings, turn to the
listed page beside the function, press the designated func-
tion menu key, then press and hold the NEXT or PREVI-
OUS key until its screen appears on the LCD. Once the
proper screen appears, simply follow the programming in-
structions given below the applicable screen in this manual.
Note: Record any changes made to the factory
preset values in the corresponding space provided.
Factory Preset
Changed
See page...
To adjust
To
to adjust
Press....
Setpoints
Leaving Solution Setpoint
44 deg F
34
SETPOINTS
Low Ambient Compressor Lockout
Temperature Setpoint
40 deg F
34
SETPOINTS
Heat Tape Temperature Setpoint
40 deg F
34
SETPOINTS
Hot Start Load Limit Setpoint
71 deg F
34
SETPOINTS
Ice Building Terminate Temperature
27 deg F
34
SETPOINTS
Low Solution Cutout Temperature
35 deg F
34
SETPOINTS
Low Ambient Pump Override Temperature
35 deg F
34
SETPOINTS
Use Leaving Solution Setpoint From:
HI STP Menu
34
SETPOINTS
Use Ice Building Terminate Setpoint From:
HI STP Menu
34
SETPOINTS
Use Hot Start Load Limit Setpoint From:
HI STP Menu
35
SETPOINTS
Use Capacity Limit Setpoint From:
No Source Selected
35
SETPOINTS
Information format
Display Text in
English Language
23
SETUP
Display Units in
English
23
SETUP
Unit Control
Local
23
SETUP
Unit Address
49
23
SETUP
General Unit Functions Setup
Delay unit Start
0 Seconds
23
SETUP
Demand Limit Definition
None
24
SETUP
Hot Gas Bypass Function
Disabled
24
SETUP
Hot Gas Bypass Max Run Time
30 Minutes
24
SETUP
Hot Start Time Interval
60 Minutes
24
SETUP
Hot Operation Response Option
50% Capacity
(Auto Reset Diag.)
24
SETUP
Pumpdown Function
Disabled
24
SETUP
Compressor Lead/Lag Function
Disabled
24
SETUP
Default Chiller Solution Pump Mode
Auto
24
SETUP
Evaporator Solution Pump Off Delay Time
30 Seconds
25
SETUP
Loop Stabilization Time
120 Seconds
25
SETUP
Low Ambient Compressor Lockout
Enabled
25
SETUP
Leaving Solution Reset Type
None
25
SETUP
Chiller Application
Comfort
25
SETUP
Evaporator Solution Flow Switch Proving
Disabled
25
SETUP
OA Temp Reset Type: Start Temp
70 deg F
25
SETUP
OA Temp Reset Type: End Temp
50 deg F
25
SETUP
OA Temp Reset Type: Max Amount of Reset
5 deg F
25
SETUP
Zone Temp Reset Type: Start Temp
78 deg F
25
SETUP
Zone Temp Reset Type: End Temp
75 deg F
25
SETUP
Zone Temp Reset Type: Max Amount of Reset
5 deg F
25
SETUP
Entering Solution Temp Reset Type: Start Temp
45 deg F
25
SETUP
Entering Solution Temp Reset Type: End Temp
40 deg F
25
SETUP
Entering Solution Temp Reset Type: Max Amount
5 deg F
25
SETUP