System Programming SETUP
Used on Units:
All Units
Possible Values:
0 to 20 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
95 to 115 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
80 to 110 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
2.0 to 10.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
25 to 66 F, Disabled
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
1. Pressing the NEXT key will display the beginning of
the Submenu.
2. Press the NEXT key again to advance to the following screen.
This screen is displayed when GBAS 0-5 VDC Module is installed
1.To view the factory preset or to modified the factory presets
to meet specific application requirements, press the
ENTER key to advance to the following screens. If no
adjustments are required, press the NEXT key to advance to
"GBAS 0-10 VDC Module I/O Assignments"
Used on Units:
With GBAS 0-5VDC Module
Possible Values:
Leaving Solution Setpoint
Ice Build Terminate Setpoint
2. Press the + or - key until the proper value is displayed.
Hot Start Load Limit Setpoint
3. Press the ENTER key to confirm this choice.
Capacity Limit Setpoint
4. Press the NEXT key to display Generic BAS Analog Input
2 screen.
5. Press the + or - key until the proper value is displayed.
6. Press the ENTER key to confirm each choice.
7. Repeat steps 1 - 4 to display Generic BAS Analog Input
screens 2, 3 & 4.
8. Press the NEXT key to advance to the following screen.
Saturated Condenser Temp Control Band
Temporary Low Limit Suppression 10 F
Saturated Condenser Temperature
Efficiency Check Point 110 F
Saturated Condenser Temperature
Low Ambient Control Point 100 F
End of Submenu (NEXT) to Re-enter STATUS
GBAS 0-5VDC Module I/O Assignment
Press ENTER to Review or Adjust
GBAS (0-5VDC) Analog Input 1 Assignment
NOT ASSIGNED
Saturated Condenser Temperature
Low Ambient Control Deadband 4.0 F
Saturated Condenser Temperature
OA Temp Supression Setpoint 40 F