K-2
2) Standard specifications by types (large capacity types)
Item
Description
Voltage class
200 V class
Applicable motor [kW]
75
90
Model No.
VFA7–
Type
2750P1
2900P1
Output capacity [kVA] (*1)
110
133
Output current [A]
288
350
Output voltage
3-phase 200 to 230 V (Maximum output voltage corresponds to input supply voltage.)
Ratings
Rated overload current
150% for 1 minute, 180% for 0.3 second (*5)
Dynamic braking
circuit
Built-in type dynamic braking drive circuit is optionally available
Electric
brakin
g
Dynamic braking
resistor
External braking resistor is available optionally
Main
circuit
3-phase 200-230 V, 50/60 Hz
Voltage,
frequency Control
circuit
Single phase 200-230 V, 50/60 Hz
Po
w
er supp
ly
Allowable fluctuation
Voltage: +10%/-15% (*3), Frequency: +/-5%
Protection structure
Open type (JEM1030) IP00 (*2)
Cooling system
Forced-air cooling
Coating color
Munsell 5Y-8/0.5
EMI filter
Option to be installed externally
Item
Description
Voltage class
400 V class
Applicable motor [kW]
90/110
132
160
220
280
Type
VFA7–
Form
4110KP1
4132KP1
4160KP1
4220KP1
4280KP1
Output capacity [kVA] (*1)
160
194
236
320
412
Output current [A]
210
255
310
420
540
Output voltage
3-phase 380-460 V (Maximum output voltage corresponds to input supply voltage.)
Ratings
Rated overload current
150% for 1 minute, 180% for 0.3 second (*5)
Dynamic braking
circuit
Built-in type dynamic braking drive circuit is optionally available
Electric
brakin
g
Dynamic braking
resistor
External braking resistor is available optionally
Main
circuit
3-phase 380-460 V, 50/60 Hz
Voltage,
frequency Control
circuit
Single phase 380-460 V, 50/60 Hz
Po
w
er supp
ly
Allowable fluctuation
Voltage: +10%/-15% (*3), Frequency: +/-5%
Protection structure
Open type (JEM1030) IP00 (*2)
Cooling method
Forced-air cooling
Coating color
Munsell 5Y-8/0.5
EMI filter
Option to be installed externally
(*1):
Rated output capacity indicates a value based on the condition that output voltage is 220 V in case of the 200 V class or
440 V in case of the 400 V class.
(*2):
The models of 30 kW or higher have neither cover for the wiring hole that has a big aperture nor space for bending
external cables inside the unit. When a protector is installed externally, use an optional cover for the wiring hole.
(*3):
Allowable voltage variation is +/-10 % in continuously operation (100 % load)
(*4):
Be sure to attach DC reactor (option) for the models: 200V class 75kW or more and 400V class 110kW or more.
(Not necessary for DC input.)
(*5):
This regulation is overload value from the stop state at ambient temperature state within regulation value.
3) Comparison between small/medium capacity types and large capacity types in specifications (different points only)
Small/medium capacity type
Large capacity type
Item
VFA7-2004PL
〜
2150P
VFA7-4007PL
〜
4150PL
VFA7-2185P
〜
2550P1
VFA7-4185P
〜
4750P1
VFA7-2750P1,2900P1
VFA7-4110KP1
〜
4280KP1
1. Rated overload
current
150 % for 2 minutes
215 % for 0.5 second
150 % for 2 minutes
215 % for 0.5 second
150 % for 1 minutes
180 % for 0.3 second
2. PWM carrier
frequency
Default setting: 12 kHz
Adjustable between 0.5 and 15 kHz
Default setting: 12 kHz
200 V class 37,45 kW type: 8 kHz
200 V class 55 kW type: 2.2 kHz
400 V class 37-55 kW type: 8 kHz
400 V class 75 kW type: 2.2 kHz
Adjustable between 0.5 and 15 kHz
2550P1,4750P1:
Adjustable between 0.5 and 8 kHz
Default setting: 2.2 kHz
Adjustable between 0.5 and 5 kHz
3.Acceleration/deceleration
time (default setting)
10 seconds
30 seconds
4750P1:60 seconds
60 seconds