Expansion TB option unit
Function
Description
16-bit binary input
(12-bit binary)
4-digit BCD code input (3-digit
BCD code)
Contact
input
Multifunction programmable
input (high-order 8 bits)
・
Sink input
ON : 5 V DC or less (5 mA type)
OFF : 11 V DC or more, or 0.5 mA or less
・
Source input
ON : 11 V DC, 2.5 mA or more (maximum 30 V DC)
OFF : 5 V DC or less, or 1.4 mA or less
Multifunction programmable analog output
(current/voltage output switchable)
・
Current: 4 to 20 mA DC output (source output)
Maximum connectable resistance: 750
Ω
・
Voltage:
±
10 V DC output
Multifunction programmable relay contact
output
・
1a, 1b contact output (double circuit)
Contact rating : 250 V AC, 2 A (cos
φ
= 1)
250 V AC, 1 A (cos
φ
= 0.4)
30 V DC, 1 A
75 kW or less model (200V class)
■
Installation of optional add-on cassettes to 132 kW or less model (400V class)
To install optional add-on cassette(s), use the attachment and set the options on the right side
of the inverter. To attach the option(s), secure an enough space in the right side of the inverter.
・
To install a cassette:
L = 48.5 mm or more
・
To install two cassettes:
L = 73.5 mm or more
・
To install three cassettes:
L = 98.5 mm or more
・
No matter for cassettes number, L1 = 20.0 mm or more
90 kW or more model (200V class)
■
Installation of optional add-on cassettes to 160 kW or more model (400V class)
To install optional add-on cassette(s), use the attachment and set the options on the right side
of the control panel. To attach the option(s), secure an enough space (L: 50 mm or more) in front
of the inverter.
L
Option cover
*
Option cover
*
Flexible connecting
board
*
Optional add-
on cassettes
L
L1
Optional add-
on cassettes
*
: In a set with SBP001Z.