F-60
=
(Disabled)
・・・・
does not trip (FL is not active).
=
(Enabled)
・・・・
The inverter trips if a torque current larger than
(during
power running) or
(during regeneration) passes for a
time longer than the time set with
.
Title
Function
Adjustment range
Default setting
Over-torque trip
: Disabled
: Enabled
Over-torque detection level during power running
〜
[%]
Over-torque detection level during regeneration
〜
[%]
Over-torque detection time
〜
[s]
6.25.10 Cooling fan control mode selection
:
Cooling fan control mode
=
:
Automatic control of cooling fan, enabled. Operates only when the inverter is in
operation.
=
:
Automatic control of cooling fan, disabled. The cooling fan always operates
when the inverter is energized.
☆
The cooling fan automatically operates whenever the ambient temperature is
high, even when the inverter is out of operation.
Title
Function
Adjustment range
Default setting
Cooling fan control mode
: Automatic
: Always ON
6.25.11 Cumulative operation time alarm
:
Cumulative operation time alarm setting
*
Panel display of
corresponds to 10 hours.
If
is displayed, the cumulative operation time
is 3855 hours.
Title
Function
Adjustment range
Default setting
Cumulative operation time
alarm setting
〜
[
×
100h]
■
Output terminal setting
Ex.) Assigning the cumulative operation time alarm function to the terminal OUT2
Title
Function
Adjustment range
Setting value
Output terminal selection#2 (OUT2)
〜
・
Function
With this parameter, you can set the condition of cooling fan so that it operates only when
the inverter requires cooling, and thus it can be used for a longer period of.
・
Function
This parameter is to make a setting so that the inverter puts out a signal when it
s cumulative operation time has reached the time set with this parameter.