J-
23
[
Monitor FM/AM/pulse output function selection
]
Communication
number
Function
Communication
unit
Monitor output
selection
Trip holding
Meter output
selection
Speed
control
Torque
control
Position
control
V/f
constant
Reference
section
0
FD00
Running frequency
0.01 [Hz]
0
(*3)
0
●/●
●/●
−/●
●
1
FE02
Frequency command
0.01 [Hz]
1
hold
1
●/●
−
−
●
2
FE03
Current
0.01 [%]
2
hold
2
●/●
●/●
−/●
●
3
FE04
DC voltage
0.01 [%]
3
hold
3
●/●
●/●
−/●
●
4
FE05
Output voltage
0.01 [%]
4
hold
4
●/●
●/●
−/●
●
5
FE15
After-compensation frequency
0.01 [Hz]
5
hold
5
●/●
●/●
−/●
●
6
FE16
Speed feedback (real-time value)
0.01 [Hz]
6
hold
6
−/●
−/●
−/●
―
7
FE17
Speed feedback (1 second filter)
0.01 [Hz]
7
hold
7
−/●
−/●
−/●
−
8
FE18
Torque
0.01 [%]
8
hold
8
●/●
●/●
−/●
●
(*2)
9
FE19
Torque reference
0.01 [%]
9
hold
9
−
●/●
−
−
10
FE56
Internal torque reference (*1)
0.01 [%]
10
hold
10
●/●
●/●
−/●
−
11
FE20
Torque current
0.01 [%]
11
hold
11
●/●
●/●
−/●
●
(*2)
12
FE21
Exciting current
0.01 [%]
12
hold
12
●/●
●/●
−/●
●
(*2)
13
FE22
PID feedback value
0.01 [Hz]
13
hold
13
●/●
−
−
●
14
FE23
Motor overload factor (OL2 data)
0.01 [%]
14
hold
14
●/●
●/●
−/●
●
15
FE24
Inverter overload factor (OL1 data)
0.01 [%]
15
hold
15
●/●
●/●
−/●
●
16
FE25
PBr overload factor (PBrOL data)
0.01 [%]
16
hold
16
●/●
●/●
−/●
●
17
FE28
PBr load factor (pulse duty)
0.01 [%]
17
hold
17
●/●
●/●
−/●
●
18
FE29
Input power
0.01 [kW]
18
hold
18
●/●
●/●
−/●
●
19
FE30
Output power
0.01 [kW]
19
hold
19
●/●
●/●
−/●
●
20
FE31
Peak output current
0.01 [%]
20
hold
20
●/●
●/●
−/●
●
21
FE32
Peak DC voltage
0.01 [%]
21
hold
21
●/●
●/●
−/●
●
22
FE33
Motor counter dummy PG
1 count
22
hold
22
●/●
●/●
−/●
●
23
FE34
Position pulse
1count
23
hold
23
−
−
−/●
−
24
FE35
PR input
0.01 [%]
24
not hold
24
●/●
●/●
−/●
●
25
FE36
VI/II input
0.01 [%]
25
not hold
25
●/●
●/●
−/●
●
26
FE37
RX input
0.01 [%]
26
not hold
26
●/●
●/●
−/●
●
27
FE38
RX2 input
0.01 [%]
27
not hold
27
●/●
●/●
−/●
●
28
FE39
FM output
0.01 [%]
28
not hold
28
●/●
●/●
−/●
●
29
FE40
AM output
0.01 [%]
29
not hold
29
●/●
●/●
−/●
●
30
FE57
Fixed output for meter adjustment
0.01 [%]
−
hold
30
●/●
●/●
−/●
●
31
FE64
Analog output for communication
0.01 [%]
−
not hold
31
●/●
●/●
−/●
●
32
FE60
Acc/dec torque removal
0.01 [%]
−
not hold
32
−/●
−/−
−/●
−
5.4
(*1): When
=7,8,9,
●/●
under speed control.
(*2): Reference data
(*3): Trip frequency is displayed in another way.
For details, refer to section 5.4; [Terminal FM-related parameters].
For monitor indications, refer to section 8.2; [Set up values of monitor indication parameters].
Communication number 31(Analog output for communication) outputs analog data of FA51.
Sensorless vector/vector with sensor
(●
: valid,
−
: invalid
)