6.13.3 Retry function
:
Retry selection
Warning
Mandatory
・
Do not get near the alarm-stopped motor and machine.
When the inverter is in retry mode, the alarm-stopped motor and machine unexpectedly
restart when the predetermined time has passed, and thus might cause you to get an injury.
・
Stick caution labels to the inverter, the motor and the machine, to prevent accidents
due to an unexpected restart of them because of the retry function.
[Parameter setting]
Title
Function
Adjustment range
Default setting
Retry selection
0: Disabled,
〜
times
Causes of tripping and retry process
Cause of tripping
Retry process
Canceling conditions
Momentary
power failure
Over-current
Over-voltage
Overload
a maximum of 10 consecutive retries
1st retry : about 1 [s] after tripping
2nd retry : about 2 [s] after tripping
3rd retry : about 3 [s] after tripping
…
10th retry : about 10 [s] after tripping
Retry is canceled if the inverter
trips again for reasons other than a
momentary power failure, over-
current, over-voltage or overload,
or if the inverter fails to restart
within the predetermined number
of retries.
Kinds of trips can be retried
・
,
,
:
Over-current
・
:
Overload of inverter
・
:
Over heat
・
,
,
:
Over-current of DC injection
・
:
Overload of motor
・
,
,
:
Over-voltage
・
:
Overload of braking resister
★
No retry is performed if the inverter trips for the following reasons:
・
,
,
: Arm short circuit
・
: Interruption communication error
・
: Phase failure(input side)
・
: Gate array fault
・
: Phase failure(output side)
・
: Output current detector error
・
: Loaded side over-current at start time
・
: Optional unit fault
・
,
: Ground-fault
・
: Flash memory fault
・
: Emergency stop
・
: Sink/source switching error
・
: EEPROM error
・
: Speed error (Over speed)
・
: Main RAM error
・
: Key error
・
: Main ROM error
・
Others
(other than the above)
・
: CPU fault
★
During a retry, the fault detection relay (FLA, B and C) is not active.
★
A virtual cooling time is set for trips due to an overload (
,
,
). Therefore, a
retry is performed after a virtual cooling time and the retry time have passed.
★
In the case of a trip due to an over-voltage (
〜
), the inverter may trips again
unless the voltage in its D.C. section falls enough.
★
In the case of a trip due to overheating (
), the inverter may trip again unless the
temperature inside it falls enough; the inverter monitors the temperature in it.
★
A retry is performed if
is set enabled, even if the trip holding selection parameter
is set at
.
★
During a retry,
and the value selected with the status monitor selection
parameter
are displayed alternately.
・
Function
The inverter automatically resets itself when it has tripped. During a retry, according to
the setting of
(Auto-restart mode selection) the inverter automatically restarts
and this function makes smooth motor activation possible.