[7] Speed/torque reference gain/bias setup (1/2)
Vector control
Title
Communi
cation No
Function
Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
Torque
control
Position
control
V/f
Constant
Reference
section
0200
Reference priority selection
0:
1:
2:
priority (*1)
3:
priority (*2)
4:
/
switching
−
0
Enabled
●
/
●
−
−
●
6.6.1
0201
VI/II reference point #1
0
〜
100 [%]
1/0.01
20.0
Enabled
●
/
●
●
/
●
−
●
7.3.2
0202
VI/II reference point #1 frequency 0.0
〜
[Hz]
0.01/0.01
0. 0
Enabled
●
/
●
●
/
●
−
●
7.3.2
0203
VI/II reference point #2
0
〜
100 [%]
1/0.01
100
Enabled
●
/
●
●
/
●
−
●
7.3.2
0204
VI/II reference point #2 frequency 0.0
〜
[Hz]
0.01/0.01
80.0
Enabled
●
/
●
−
−
●
7.3.2
0205
VI/II reference point #1 rate
-250
〜
250 [%] (For torque control, etc.)
1/0.01
0
Enabled
●
/
●
●
/
●
−
−
6.21.1
0206
VI/II reference point #2 rate
-250
〜
250 [%] (For torque control, etc.)
1/0.01
100
Enabled
●
/
●
●
/
●
−
−
6.21.1
0207
Speed setting mode selection #2 Same as
(1 to 11)
−
1
Enabled
●
/
●
−
−
●
6.61
0208
/
switching frequency 0.1
〜
[Hz]
0.01/0.01
1.0
Enabled
●
/
●
−
−
●
6.6.1
0209
Analog input filter
0(Disabled) to 3(Max. filter capacity)
−
0
Enabled
●
/
●
●
/
●
−
●
7.2.4
0210
RR reference point #1
0
〜
100 [%]
1/0.01
0
Enabled
●
/
●
●
/
●
−
●
7.3.1
0211
RR reference point #1 frequency 0.0
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
7.3.1
0212
RR reference point #2
0
〜
100 [%]
1/0.01
100
Enabled
●
/
●
●
/
●
−
●
7.3.1
0213
RR reference point #2 frequency 0.0
〜
[Hz]
0.01/0.01
80.0
Enabled
●
/
●
−
−
●
7.3.1
0214
RR reference point #1 rate
0
〜
250 [%] (For torque control, etc.)
1/0.01
0
Enabled
●
/
●
●
/
●
−
−
6.21.1
0215
RR reference point #2 rate
0
〜
250 [%] (For torque control, etc.)
1/0.01
100
Enabled
●
/
●
●
/
●
−
−
6.21.1
0216
RX reference point #1
-100
〜
100 [%]
1/0.01
0
Enabled
●
/
●
●
/
●
−
●
7.3.3
0217
RX reference point #1 frequency -
〜
[Hz] (*3)
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
7.3.3
0218
RX reference point #2
-100
〜
100 [%]
1/0.01
100
Enabled
●
/
●
●
/
●
−
●
7.3.3
0219
RX reference point #2 frequency -
〜
[Hz] (*3)
0.01/0.01
80.0
Enabled
●
/
●
−
−
●
7.3.3
0220
RX reference point #1 rate
0
〜
250 [%] (For torque control, etc.)
1/0.01
0
Enabled
●
/
●
●
/
●
−
−
6.21.1
0221
RX reference point #2 rate
0
〜
250 [%] (For torque control, etc.)
1/0.01
100
Enabled
●
/
●
●
/
●
−
−
6.21.1
0222
RX2 reference point #1
-100
〜
100 [%]
1/0.01
0
Enabled
●
/
●
●
/
●
−
●
※
0223
RX2 reference point #1 frequency -
〜
[Hz] (*3)
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
※
0224
RX2 reference point #2
-100
〜
100 [%]
1/0.01
100
Enabled
●
/
●
●
/
●
−
●
※
0225
RX2 reference point #2 frequency -
〜
[Hz] (*3)
0.01/0.01
80.0
Enabled
●
/
●
−
−
●
※
0226
RX2 reference point #1 rate
-250
〜
250 [%] (For torque control, etc.)
1/0.01
0
Enabled
●
/
●
●
/
●
−
●
※
0227
RX2 reference point #2 rate
-250
〜
250 [%] (For torque control, etc.)
1/0.01
100
Enabled
●
/
●
●
/
●
−
●
※
(*1): When setup frequency(signal set up by
) is
or more, signal set up by
is accepted, When setup frequency is lower than
, the inverter runs under the signal of
.
(*2): When setup frequency(signal set up by
) is
or more, signal set up by
is accepted, When setup frequency is lower than
, the inverter runs under the signal of
.
(*3): Adjustment range is -327.68
〜
327.67 [Hz] in case of 16-bit access.
※
(Reference section): Refer to the inverter's individual manual.
Sensorless vector/vector with sensor (
●
valid,
−
:invalid)