F-45
voltage signals
current signals
6.22 Torque limit
:
Selection of power running torque limit #1
:
Power running torque limit #1
:
Selection of regenerative torque limit #1
:
Regenerative torque limit #1
:
Power running torque limit #2
:
Regenerative torque limit #2
:
Power running torque limit #3
:
Regenerative torque limit #3
:
Power running torque limit #4
:
Regenerative torque limit #4
:
Torque limit mode (polarity)
■
Setting
(1) Power running /regenerative torque limit
First, you need to set the polarity of each torque limit. Set
at
.
Title
Function
Adjustment range
Setting value
Torque limit
mode (polarity)
: Power running/regenerative torque limit
: Positive/negative torque limit
a
)
limiting the torque with internal parameters (or on communication mode)
Torque limits can be set with the parameters
and
.
[Setting of power running torque]
(Selection of power running torque limit #1) :Set at
(
)
(Power running torque limit #1)
:Set a desirable torque limit level.
[Setting of regenerative torque]
(Selection of regenerative torque limit #1)
:Set at
(
)
(Regenerative torque limit #1)
:Set a desirable torque limit level.
・
Function
The function is to decrease or increase the output frequency according to the load
ing condition when the motor torque reaches the limit level.
Setting a torque limit parameter at 250.0 means "Invalid".
+
250% torque
−
250% torque
Power running
Regenerative
Forward
Reverse
Power running
Regenerative
RR-CC
――
0
〜
10V
(0
〜
250%)
RX-CC
――
0
〜±
10V (0
〜
250%)
VI-CC
――
0
〜
10V
(0
〜
250%)
II-CC
――
4(0)
〜
20mA (0
〜
250%)
,