Appendix – Specifications
Grounding Requirements
Strata AirLink Installation Guide 5/00
99
Grounding Requirements
Table 37
provides the recommended gauges for the distances between the system and the master
ground bus of the office telephone system. The proper gauge wire ensures that DC resistance does
not exceed 0.25 ohms.
FCC
The Strata AirLink wireless telephone system operates under the FCC Part 15 rules for Unlicensed
Personal Communications Service (UPCS) equipment in the 1920~1930 MHz band.
Note
Part 15 ID numbers for the Base Station (BS) and handset are BS-CJ6DT-WRLS-BS-01
and HS-CJ6DT-WRLS-HS-01, respectively. The system complies with UL1459 for safety,
and the compliance ID is C86-0345.
Part 68
The Strata AirLink Wireless telephone system complies with Part 68 of FCC rules. Product labels
contain, along with other information, the FCC registration number. This information must be
provided to the telephone company if they request it.
Note
The FCC Part 68 registration number is 5RYISR-23723-WC-T, and the Ringer
Equivalence Number (REN) is 0.6B.
An FCC-compliant telephone cord with modular plug is provided with the system hardware. This
equipment is designed for telephone networks or premises wiring using a compatible modular jack
that is Part 68 compliant.
If the wireless equipment causes harm to the telephone network, the telephone company will give
advance notification. If advance notice is not practical, the telephone company will give
notification as soon as possible. Along with the notification, the telephone company will advise of
the right to file a complaint with the FCC, if necessary.
To report trouble with the wireless equipment, please contact Toshiba America Information
Systems, Inc., Telecommunications Systems Divisions in Irvine, CA, (949) 583-3700 for repair
and/or warranty information. If the trouble is causing harm to the public telephone network, the
telephone company can request that the wireless equipment be removed from the network until the
problem is resolved.
Important!
Repairs must be made by an authorized representative or the warranty is void.
Table 37
Ground Wire Requirements
StrataAirLink:Distance
Between
BSIA/RWIU & Ground
Recommended
Gauge
0~18 feet
16 AWG
0~30 feet
14 AWG
0~46 feet
12 AWG
0~73 feet
10 AWG
0~113 feet
8 AWG
Summary of Contents for Strata AirLink
Page 6: ...Contents Chapter 5 Maintenance and Troubleshooting iv Strata AirLink Installation Guide 5 00 ...
Page 10: ...Introduction Related Documents Media viii Strata AirLink Installation Guide 5 00 ...
Page 28: ...Pre installation Step 10 Mount Base Stations 18 Strata AirLink Installation Guide 5 00 ...
Page 106: ...Maintenance and Troubleshooting Troubleshooting 96 Strata AirLink Installation Guide 5 00 ...