– 111 –
Table 1. Setting data (CODE No. table (example))
DN
01
02
03
06
OF
10
11
12
13
14
1E
28
2A
2b
31
32
40
5d
60
C2
d0
d1
Item
Filter sign lighting time
Filter pollution leve
Central control address
Heating suction temperature shift
Cooling only
Type
Indoor unit capacity
System address
Indoor unit address
Group address
Temperature range of cooling/heating
automatic SW control point
Power failure automatic recovery
Option/Abnormal input (CN70) SW
Thermo output SW (T10
)
Ventilation fan (standalone)
Sensor SW (Selection of static pressure)
Humidifier control (+ drain pump control)
External static pressure
Timer setting (wired remote controller)
Demand setting
(outdoor unit current demand)
Remote controller operation save function
Frost protection function
Setting data
Factory-set value
Depending on Type
0000: standard
0099: Not determined
0002: +2°C
(flooring installation type: 0)
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
0003: 3 deg (Ts ± 1.5)
0000: None
0002: Humidifier
0000: Thermo ON
0000: Not available
0000: Body sensor
0003: Humidifier ON + Pump OFF
0000: Standard (10Pa)
0001: High static pressure 1 (20Pa)
0003: High static pressure 2 (35Pa)
0006: High static pressure 3 (50Pa)
0000: Available
0075: 75 %
0001: Enable
0000: None
Table 2. Type: CODE No. 10
Table 3. Indoor unit capacity: CODE No. 11
∗
EEPROM initial value on the P.C. board for indoor unit servicing.
Setting data
0005
Type
Slim Duct Type
Type name abb.
RAV-SM
∗∗∗
SDT-E
Setting data
0000*
0006
0007
0009
0012
0015
0017
0018
Type
Disable
40
45
56
80
110
140
160