– 73 –
∗
1: These are representative examples and the check code differs according to the outdoor unit to be combined.
Lamp indication
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Simultaneous flash
Check code
F01
F02
P10
F04
F06
F07
F08
F12
F13
F15
F29
F31
H01
H02
H03
H04
L03
L07
L08
L09
L10
L20
L29
L30
Cause of trouble occurrence
Heat exchanger sensor (TCJ) error
Heat exchanger sensor (TC) error
Indoor unit sensor error
Heat exchanger sensor (TA) error
Discharge temp. sensor (TD) error
Temp. sensor (TE) error
Temp. sensor (TL) error
Temp. sensor (TO) error
Sensor error of outdoor unit
∗
1
Temp. sensor (TS) error
Temp. sensor (TH) error
Temp. Sensor miswiring (TE, TS)
Indoor EEPROM error
Outdoor EEPROM error
Compressor break down
Compressor lock
Current detection circuit error
Outdoor compressor system error
∗
1
Case thermostat worked.
Duplicated master indoor units
There is indoor unit of group connection
→
AUTO address
in individual indoor unit.
∗
If group construction and
Unsetting of group address
address are not normal
Missed setting
when power supply turned on,
(Unset indoor capacity)
automatically goes to address
setup mode.
Unset model type (Service board)
Duplicated indoor central addresses
Other error of outdoor unit
Others
Outside interlock error