– 49 –
No.
6
Item
Air speed
selection
(Continued):
In case of
Slim Duct Type
Outline of specifications
Slim Duct Type
Slim Duct Type
3) In heating operation, the mode changes to [UL] if
thermostat is turned off.
4) If Ta
≥
25°C when heating operation has started and when
defrost operation has been cleared, the air conditioner
operates with (H) mode or higher mode for 1 minute after
Tc entered in E zone of cool air discharge preventive
control (Item 7).
Remarks
Selection of high static
pressure type
Item code:
[5d] or selection of high
static pressure on P.C.
board SW501
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
SM40
SM45
SM56
Revolution speed (rpm)
1260
1260
1320
1180
1180
1220
1120
1120
1220
1040
1040
1220
1020
1020
1180
990
990
1180
960
960
1180
950
950
1040
910
910
990
870
870
990
840
840
880
790
790
820
550
550
550
Item code
[5d]
SW501 (1)/(2)
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
Standard
Type 1
Type 3
Type 6
0
1
3
6
OFF/OFF
ON/OFF
OFF/ON
ON/ON
HEAT COOL HEAT COOL HEAT COOL HEAT COOL
HH
HH
HH
HH
H+
H+
H
H
HH
HH
H+
H+
H
H
L+
L+
HH
HH
H+
H+
H
H
L+
L+
H+
H+
H
H
L+
L+
L+
L+
L
L
LL
LL
LL
LL
LL
LL
LL
LL